Advanced Operation
Set Values
• These parameters prevent the motor from over excitation due to voltage changes during energy-sav-
ing control.
• Set the upper limit of output voltage in percentage at each frequency based on the rated motor voltage
as 100%.
• Normally, the default settings do not need to be changed.
Output voltage
upper limit (%)
n144
Probe Operation Voltage Limit
Setting
0 to 100 (%)
range
Set Values
• When the output frequency is constant for a certain period while the Inverter is in effective energy-sav-
ing control, the Inverter will be set to the primary level of energy-saving control by n140 (energy-saving
constant K2). Then the Inverter will be set to the secondary level (i.e., probe operation) for more effi-
cient, energy-saving control. Set the control voltage range of the Inverter in probe operation in param-
eter n144.
• Set the upper limit of probe operation voltage in percentage based on the rated motor voltage as
100%. Normally set the value to approximately 10%.
• No probe operation will be available if the value is set to 0.
n145
Probe Operation Control Voltage
Step at 100%
Setting
0.1 to 10.0 (%)
range
n146
Probe Operation Control Voltage
Step at 5%
Setting
0.1 to 10.0 (%)
range
Output frequency (Hz)
Register
0190 Hex
Unit of
1%
setting
Register
0191 Hex
Unit of
0.1%
setting
Register
0192 Hex
Unit of
0.1%
setting
Chapter 6
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0.5
Changes during
No
operation
Default setting
0.2
6-9