Communications
Set Values
Value
0
Detects a time-over and fatal error and coasts to a stop (See note 1.)
1
Detects a time-over and fatal error and decelerates to a stop in deceleration time 1 (See note 1.)
2
Detects a time-over and fatal error and decelerates to a stop in deceleration time 2 (See note 1.)
3
Detects a time-over and nonfatal error warning and continues operating. The warning is
canceled when the communications return to normal. (See note 2.)
4
No time-over is detected.
Note 1. The fatal error is canceled with error reset input.
Note 2. The nonfatal error warning is canceled when the communications returns to normal.
H Communications Frequency Reference/Display Unit Selection (n152)
• Set this parameter to the unit of frequency reference and frequency-related values to be set or moni-
tored through communications.
• This unit is for communications use only and independent from the units of setting made through the
Digital Operator.
n152
RS-422/485 Communications
Frequency Reference/Display Unit
Selection
Setting
0 to 3
range
Set Values
Value
0
0.1 Hz
1
0.01 Hz
2
Converted value based on 30,000 as max. frequency
3
0.1% (Max. frequency: 100%)
Note Communications data after the above conversion is hexadecimal.
For example, if the frequency is 60 Hz and the unit of setting is 0.01 Hz, the converted value is
obtained as follows:
60/0.01 = 6000 = 1770 Hex
H Slave Address (n153)
• Set this parameter to the Slave address (Slave unit number) for communications.
• If more than one Inverter is connected as a Slave, make sure that there will be no Slave address
duplication.
n153
RS-422/485 Communications
Slave Address
Setting
00 to 32
range
Set Values
Value
00
Only receives broadcast messages from the Master (See note.)
01 to 32
Slave address
Description
Register
0198 Hex
Unit of
1
setting
Description
Register
0199 Hex
Unit of
1
setting
Description
Chapter 7
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
00
7-3