Omron SYSDRIVE 3G3MV SERIES User Manual page 327

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

List of Parameters
Para
Reg-
Name
me-
ister
ter
No.
No.
(Hex)
n115
0173
Stall pre-
vention
level auto-
matic sup-
pression
selection
n116
0174
Stall pre-
vention ac-
celeration/
decelera-
tion time
setting
n117
0175
Undertor-
que detec-
tion func-
tion selec-
tion
n118
0176
Undertor-
que detec-
tion level
n119
0177
Undertor-
que detec-
tion time
Note These parameters are available on 200-V/400-V, 4.0-kW (or less) Inverters (software version
VSP010024 or higher) or 5.5-kW/7.5-kW Inverters (VSP010104 or higher).
Description
Selects whether or not to automatically de-
crease the level for stall prevention during op-
eration if the frequency lies in a constant out-
put range exceeding the frequency set in n013
for max. voltage frequency (a range greater
than the rated motor frequency).
0: Automatic suppression function disabled
(the value of n094 is valid for any frequency)
1: Automatic suppression function enabled.
* The operation level is decreased by n094 ×
(max. voltage frequency/output frequency).
* The stall prevention function during opera-
tion operates according to the acceleration/
deceleration time set in n116.
Sets the acceleration/deceleration time for the
stall prevention function during operation.
0: Accelerates or decelerates according to ac-
celeration/deceleration time 1 or 2, whichev-
er is selected.
1: Accelerates or decelerates according to ac-
celeration/deceleration time 2 (n021/n022).
* When a faster (or slower) acceleration/de-
celeration time is desired, set this parameter
to "1" and set the desired acceleration/de-
celeration time for stall prevention operation
in acceleration/deceleration time 2.
0: Undertorque detection disabled
1: Undertorque detection only when speed
coincides and operation continues (UL3
Warning)
2: Undertorque detection only when speed
coincides and output turned OFF (UL3
Fault)
3: Undertorque always detected and operation
continues (UL3 Warning)
4: Undertorque always detected and output
turned OFF (UL3 Fault)
Used to set undertorque detection level.
Detection from output torque: Set as a
percentage based on the rated motor torque as
100%.
Detection from output current: Set as a
percentage based on the rated Inverter output
current as 100%.
Used to set the detection time for undertorque.
Undertorque will be detected if a torque that is
equal to or less than the undertorque detection
level continues for the time set here.
Chapter 10
Set-
Unit
Defa
Chan-
ting
of
ult
ges dur-
range
set-
set-
ting
ting
opera-
0, 1
1
0
No
0, 1
1
0
No
0 to 4
1
0
No
10
(See
note.)
0 to
1%
10%
No
200
10
(See
note.)
0.1 to
0.1 s
0.1 s
No
10.0
10
(See
note.)
Ref-
er-
ing
ence
page
tion
6-29
6-30
6-32
6-33
6-34
10-25