Frequency Detection - Omron SYSDRIVE 3G3MV SERIES User Manual

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Advanced Operation

6-10-8 Frequency Detection

• The 3G3MV has the following frequency detection functions.
Frequency Detection:
Detects that the frequency reference coincides with the output frequency.
Frequency Detection Levels 1 and 2:
Detects that the output frequency is the same as or higher or lower than the set value (frequency
detection level) in n095.
• The multi-function outputs (n057 to n059) must be set for the frequency detection function.
H Frequency Detection
• The multi-function outputs (n057 to n059) must be set to the following in order to issue an output indi-
cating that the frequency reference and the output frequency agree.
Set value: 2 for frequency agree
Frequency Detection Operation
Output
frequency
Frequency
detection
H Frequency Detection Levels 1 and 2
• The parameters in n057 to n059 for multi-function output must be set for frequency detection output.
Set value: 4 for frequency detection level 1 (Output frequency y n095)
Set value: 5 for frequency detection level 2 (Output frequency x n095)
• Set the frequency detection level in n095.
n095
Frequency Detection Level
Setting
0.00 to 400.0 (Hz)
range
Set Values
• Set the frequency to be detected.
6-44
Detection width ±2 Hz
Register
Unit of
setting
Reset width ±4 Hz
Frequency reference
015F Hex
Changes during
operation
0.01 Hz
Default setting
Chapter 6
Time
Time
No
0.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents