Slip Compensation Function

The slip compensation function calculates the motor torque according to the output cur-
rent, and sets gain to compensate for output frequency.
This function is used to improve speed accuracy when operating with a load. It is mainly
valid for V/f control.
Set the rated motor current (n036) and the motor no-load current (n110) before using the
slip compensation function. If n036 = 0, the slip compensation function cannot be used.
n106
Rated Motor Slip
Setting
0.0 to 20.0 (Hz)
range
Note The default setting varies with the capacity of the Inverter model.
Set Values
• Set the rated slip value of the motor in use.
• This parameter is used as a slip compensation constant.
• Calculate the rated motor slip value from the rated frequency (Hz) and rpm on the motor nameplate by
using the following formula.
Rated slit value (Hz) + Rated frequency (Hz) –
n111
Slip Compensation Gain
Setting
0.0 to 2.5
range
Note 1. If set to vector control mode, the default value will be 1.0.
Note 2. This parameter is disabled with the value set to 0.0.
Set Values
• Set the parameter to 1.0 first and check the operation of the Inverter. Then fine-tune the gain with
0.1-gain increments or decrements.
If the speed is lower than the target value, increase the set value.
If the speed is higher than the target value, decrease the set value.
n112
Slip Compensation Primary Delay
Time
Setting
0.0 to 25.5 (s)
range
Note If set to vector control mode, the default value will be 0.2.
Set Values
• This parameter is used for the response adjustment of the slip compensation function.
• The default setting does not need any changes in normal operation.
• Change the default setting in the following cases.
The motor vibrates:
The motor response is low:
Register
Unit of
setting
Rated rpm
Register
Unit of
setting
Register
Unit of
setting
Set the value to a larger value.
Set the value to a smaller value.
016A Hex
Changes during
operation
0.1 Hz
Default setting
Number of poles
120
016F Hex
Changes during
operation
0.1
Default setting
0170 Hex
Changes during
operation
0.1 s
Default setting
Chapter 6
Yes
(See
note.)
Yes
0.0
(See
note 1.)
No
2.0 (See
note.)
6-37