7. 3. 1 Setup by analog input signals (RR terminal)

If a variable resistor (1-10 kΩ, 1/4 W) for setting up frequency is connected with the RR terminal,
the inverter can be run and stopped with external commands.
For bringing this function into practice, connect a potentiometer to the terminals of PP, RR and
CC so as to divide the reference voltage (10 VDC) at the terminal PP and to input 0 to 10 VDC of
divided voltage between the RR and CC terminals.
If analog voltage signal of 0 to 10 VDC is input between the terminals of RR and CC, frequency
can be set up without connection of a potentiometer.
<Related parameters>
Title
 Operation command mode selection
 Speed setting mode selection
 FM terminal meter selection
FM terminal meter adjustment

 Reference priority selection
 Analog input filter
 RR reference point #1
 RR reference point #1 frequency
 RR reference point #2
 RR reference point #2 frequency
 RR reference point #1 rate
 RR reference point #2 rate
MCCB
Power
supply
Function
CHARGE
U/T1
R/L1
VF−P7
S/L2
V/T2
T/L3
W/T3
RES
S1
S2
FLA
S3
FLB
S4
FL
FLC
ST
F
P24
R
OUT1
FM
OUT2
AM
FP
G/E
CC
CC RX
VI II RR PP
1∼10kΩ−1/4W
G-11
Adjustment range
∼
∼
∼
∼
(Disabled) to
 (Max. filter capacity)
∼ [%]
∼ [Hz]
∼ [%]
∼ [Hz]
∼ [%]
∼ [%]
Run/stop setup
To control switching between forward
Motor
rotation (F) and reverse rotation (R),
run and stop by external commands.
IM
■ Setup of frequency setting signal and
running frequency characteristic
To set up frequency setting signal to be
input to the potentiometer (RR terminal)
and characteristic of running frequency.
Frequency characteristic is set up at
the two points of RR reference point #1
()/frequency(), RR
reference point #2()/frequency
().
■ Connection and calibration of
frequency meter
Forward rotation
Connect a 1 mADC full-scale DC
current meter, 7.5 VDC full-scale DC
Reverse rotation
voltmeter or rectifier type AC voltmeter.
For calibration of the meter, refer to the
Frequency
section 5.4.
meter
[Hz]



0%
(0V
Frequency setting signal
Default value
Setup value
(Terminal)
(Terminal)
(RR)
(RR)
()
()








Point 2
Point 1

100%
10V)
[%]