7.3.1 Setup by analog input signals (RR/S4 terminal)

If a potentiometer (1~10kΩ-1/4W) for setting up frequency is connected with the RR/S4 terminal, the inverter can be
run and stopped with external commands.
For bringing this function into practice, connect a potentiometer to the terminals of PP, RR/S4 and CC so as to divide
the reference voltage (10Vdc) at the terminal PP and to input 0 to 10Vdc of divided voltage between the RR/S4 and CC
terminals.
If analog voltage signal of 0 to 10Vdc is input between the terminals of RR/S4 and CC, frequency can be set up without
connection of a potentiometer.
Title
Command mode selection

Frequency setting mode selection 1

FM terminal meter selection

FM terminal meter adjustment

Frequency priority selection

Analog input filter

RR/S4 input point 1 setting

RR/S4 input point 1 frequency

RR/S4 input point 2 setting

RR/S4 input point 2 frequency

*1: Inverter with a model number ending with -WN: 60.0 -WP: 50.0
MCCB
Power
supply
Function
 ~ 
 ~ 
 ~ 
-
 , 
 (No filter)~  (Max.
filter)
 ~  %
 ~  Hz
 ~  %
 ~  Hz
CHARGE
U/T1
VF-PS1
R/L1
V/T2
S/L2
W/T3
T/L3
RES
S1
S2
FLA
S3
FLB
FLC
F
P24/PLC
R
PWR
OUT1
FM
OUT2
AM
NO
CC
CC
CCA RX
VI/II
RR/S4
PP
1~10kΩ-1/4W
G-11
Adjustment range
Default setting
 (Terminal)
 (RR/S4)
-


*1
Run/stop setup
To control switching between forward run
Motor
(F) and reverse run (R), and stop by
external commands.
IM
Setup of frequency setting signal and
running frequency characteristic
To set up frequency setting signal to be
input to the potentiometer (RR/S4
terminal) and characteristic of running
frequency.
Frequency characteristic is set up at the
two points of RR/S4 reference point 1
(  )/frequency (  ), RR/S4
reference point 2 ()/frequency
(  ).
Connection and calibration of
Forward run
frequency meter
Connect a 1mAdc full-scale DC current
Reverse run
meter, 7.5Vdc full-scale DC voltmeter or
rectifier type AC voltmeter. For
calibration of the meter, refer to the
Section 5.16.
Frequency
Hz
meter

Point 1
Operation
frequency


  0%        100%
(0V     ~   
Frequency setting
E6581386
Example of setting
 (Terminal)
 (RR/S4)
-


*1
7
Point 2
%

10V)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents