Testing The Mmdu - Nortel Meridian 1 Succession 1000M Installation And Configuration Manual

Large system
Hide thumbs Also See for Meridian 1 Succession 1000M:
Table of Contents

Advertisement

Page 294 of 376

Testing the MMDU

553-3021-210
Standard 1.00
Performing acceptance tests
3
Set the line transfer switch on the attendant console associated with the
PFTU to ON. Associated attendant consoles should display a major
alarm.
4
Set the line transfer switch on the attendant console associated with the
PFTU to OFF. The "major" alarm condition displayed on attendant
consoles associated with the PFTU should disappear.
5
Repeat step 2 and step 3 for each attendant console associated with the
PFTU.
6
Set the line transfer switch on the PFTU to BYPASS and test the
telephones and trunks connected to the PFTU.
Place an outgoing call from each telephone associated with the
PFTU. Each telephone should be connected directly to a trunk.
Place an incoming call on each trunk associated with the PFTU. Each
trunk should be connected directly to a telephone.
7
Set the line transfer switch on the PFTU to NORMAL, and test the
telephones and trunks connected to the PFTU. The telephones and
trunks associated with the PFTU should return to normal operation.
Use Procedure 63 to test the MMDUs.
Procedure 63
Testing the MMDUs
1
Log into the system:
LOGI (password)
2
Enter the program:
LD 137
3
Make sure the CMDU to be tested is not disabled:
STAT CMDU
4
If the CMDU to be tested is disabled, enable it:
ENL CMDU x
October 2003
End of Procedure
checks the status of both CMDUs
x represents the number for the specific CMDU