Connecting a terminal to a CPSI port
553-3021-210
Standard 1.00
Connecting a system terminal or modem
Terminals connected to the CPSI/COM1 ports can be installed as follows.
1
One terminal connects to a CPSI/COM1 port in one CPU (the cable is
switched from module to module as needed); one terminal is required in
addition to the terminal for the SDI port connection (see Figure 59 on
page
139).
2
One terminal connects to a switch box that connects to a CPSI/COM1
port in each CPU; one terminal and a switch box are required in addition
to the terminal for the SDI port connection (see Figure 60 on
3
One terminal connects to a switch box that connects to an SDI port and
to a CPSI/COM1 port in each CPU; one terminal and a switch box are
required (see Figure 61 on
Use Procedure 18 to connect a CPSI/COM1 port directly (no switch box) to
a terminal (see Figure 59 on
Procedure 18
Connecting a terminal to a CPSI port
1
Set the terminal to 9600 baud, 7 data, space parity, one stop bit, full
duplex, XON.
2
Connect an NT8D95 cable to a matching connector on the terminal.
3
Connect the NT8D95 cable to J25 on the I/O panel in the rear of the cPCI
Core/Network Module.
4
If you are using only one terminal for both CPSI/COM1 ports, switch the
cable as needed. The terminal connected to the SDI port always
communicates with the active CPU.
October 2003
page
142).
page
139).
End of Procedure
page
140).