Nortel Meridian 1 Succession 1000M Installation And Configuration Manual page 62

Large system
Hide thumbs Also See for Meridian 1 Succession 1000M:
Table of Contents

Advertisement

Page 62 of 376
Installing ac power
553-3021-210
Standard 1.00
Figure 28
PDU ground lug locations
4
Connect the safety ground/protective earth wire (insulated ground wire
must be used for system grounding).
a.
For a single-column system, connect a #6 AWG wire from the
ground source in the service panel to a ground lug on the pedestal.
b.
For a multiple-column system, connect a #6 AWG wire from the
ground source in the service panel to a ground lug on the closest
column. Daisy-chain #6 AWG ground wires from one pedestal to the
next as illustrated in Figure 29, connecting all of the columns
together. You can also run a #6 AWG wire from the ground source to
each column individually. If the columns are not bolted together,
physically separated groups of columns should be grounded
individually as shown in Figure 27 on
Figure 29
Ac column ground lug daisy chain connection
+
+
MAIN
CIRCUIT
BREAKER
ON
+
+
+
From
ground source
October 2003
+
+
+
MAIN
CIRCUIT
BREAKER
ON
ON
ON
+
+
+
+
+
+
PDU
8D53CB
Ground lugs
+
+
+
+
+
ON
ON
+
+
+
PDU
8D53CB
To ground/protective
earth lug of next column
+
+
+
+
553-8993
page
60.
+
+
+
+
MAIN
CIRCUIT
BREAKER
ON
ON
ON
+
+
+
+
+
+
PDU
8D53CB
Terminate on
last column
+
+
+
553-8992