Installing dc power

Installing the NT4N49AA Four Feed PDU

Installing safety ground/protective earth wiring
553-3021-210
Standard 1.00
Installing the NT4N49AA PDU is a two-step process. It involves:
1
Installing safety ground/protective earth wiring on
2
Connecting power from the power plant to the NT4N49AA PDU on
page 92
Note: For installation in the UK, refer to the procedure Connecting UK
power to the NT4N49AA PDU on
CAUTION
System Failure
Failure to follow grounding procedures can result in
unsafe or faulty equipment. See Large System:
Planning and Engineering (553-3021-120) for a
complete description of approved ground sources
and methods.
Procedure 8
Installing safety ground/protective earth wiring
1
Remove the associated 30-amp fuse or set circuit breakers to the OFF
position in the power plant to disconnect each pedestal from the power
source.
2
Remove the air intake grill from the rear of the pedestal.
3
At the rear of the pedestal, use a Phillips screwdriver to remove the metal
cover over the terminal block to access the safety ground/protective earth
lugs. Leave the cover off until all pedestal connections are made.
4
Connect the safety ground/protective earth wire.
Note: Use only insulated ground wire for system grounding.