Operating
6.3 Remote operation
6.3.6.6
Echo profile data logging
You can store up to 60 profiles at a selected interval (maximum 60 minutes). Inside Echo
Profile Utilities, in the Echo Profile Time Based Storage window:
1. Enter the desired interval between stored profiles.
2. Enter the desired number of profiles to be stored (maximum 60).
3. Click on Start. A message appears warning of the time delay and warning that all previous
saved profiles will be overwritten. Click on OK to proceed. The new profiles will be saved
with their date and time.
4. Click on the tab View Saved Echo Profiles to view the stored profiles
6.3.6.7
TVT Shaper
Note
Double click on each axis to see the Xscale and Data Scale values. Right-click or Left-click on
the axis and drag to reposition the scale.
This feature allows you to manually adjust the TVT to avoid false echoes caused by
obstructions. [For an explanation see Auto False Echo Suppression (Page 182)]
Open the menu Device – Echo Profile Utilities and click on the tab TVT Shaper
①
②
③
68
TVT
Cursor
Echo profile
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF