Time Since Last Calibration (4.5.2.); Time Until Next Calibration (4.5.3.); Reminder Activation (4.5.4.); Reminder 1 (Required) (4.5.5.) - Siemens SITRANS L Operating Instructions Manual

Radar transmitters with profibus pa
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

7.5.5.2

Time since last calibration (4.5.2.)

Time elapsed since last calibration. Can be reset to zero after performing a calibration. Can be
reset locally by entering 0 in this parameter.
To reset to zero:
• In SIMATIC PDM, open the menu Device – Maintenance, click on the Calibration Schedule
tab, and click on Calibration Performed to restart the timer and clear any fault messages.
• Via the handheld programmer, manually reset Time since Last Calibration (4.8.1.) to
zero.
7.5.5.3

Time until next calibration (4.5.3.)

Read only. Calibration interval (4.5.1.) (Page 132) less Time since last calibration (4.5.2.)
(Page 133).
7.5.5.4

Reminder activation (4.5.4.)

Note
Access
To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu
Device > Maintenance.
Factory setting:
Setting range:
Purpose:
Description:
7.5.5.5

Reminder 1 (required) (4.5.5.)

Factory setting:
Setting range:
Purpose:
Description:
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
Timer OFF
Timer OFF
ON NO LIMITS
ON REMinders 1 and 2 checked
ON REMinder 2 (Maintenance Demanded) checked
Allows you to enable a maintenance reminder.
1. First set the values in Reminder 1 (required) (4.5.5.) (Page 133) Re-
minder 2 (demanded) (4.5.6.) (Page 134).
2. Select the desired Reminder Activation option.
0.164 years
0 to 20 years
If Time until next calibration (4.5.3.) (Page 133) is equal to or less than this
value, the device generates a Maintenance Required reminder.
1. Modify values as required.
2. Set Reminder activation (4.5.4.) (Page 133) to the desired option.
Parameter assignment
7.5 Service (4.)
133