Siemens SITRANS L Operating Instructions Manual page 87

Radar transmitters with profibus pa
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Parameter
type
Quick start
wizard parame-
ters
Independent
parameters
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
Sensor reference point
0.5 m
High calibration point
3.5 m
Low calibration point
Parameter name/No.
Material (1.2.)
Response Rate (1.3.)
Units (1.4.)
Operating Mode (1.5.)
Low calibration point
(1.6.)
High calibration point
(1.7.)
Apply? (apply changes)
(1.8.)
Vessel Shape (2.4.1.1.)
Maximum Volume
(2.4.1.2.)
Dimension A (2.4.1.2.)
Dimension L (2.4.1.4.)
Loe Timer (2.3.6.)
Mode (2.6.9.1.)
Value (2.6.9.2.)
A=0.8 m
L=6 m
Volume reading
100%=8000 L
Options/Values
Function
LIQUID
MED
Medium=1 m/minute
M
meters
LEVEL
Level is reported as Volume when
a vessel shape is selected
5
3.5 m (11.48 ft)
0.5
0.5 m (1.64 ft)
YES
Transfers Quick Start settings to
device
PARABOLIC ENDS
Defines vessel shape
8000
8000 liters
0.8
0.8 (2.62 ft)
6
6 m (19.68 ft)
2
2 minutes
Substitute value
User-defined value to be used
4.5
4.5 m (14.76 ft)
Operating
6.4 Application examples