Commissioning
6.1 Operating via the handheld programmer
6.1.3.6

Requesting an Echo Profile

• In PROGRAM mode, navigate to: Level Meter > (3.) >
Diagnostics > (3.1.) > Echo Profile
• Press RIGHT arrow
• Use UP
feature becomes active.
• To move a cross-hair, press RIGHT
decrease.
• To Zoom into an area, position the intersection of the cross-hairs at the center of that
area, select Zoom, and press RIGHT
• To update the profile, select Measure and press RIGHT
• To return to the previous menu, select Exit then press RIGHT
48
to request a profile.
or DOWN
arrow to scroll to an icon. When an icon is highlighted, that
confidence
algorithm: tF (trueFrist)
distance
TVT
echo
arrow to increase the value, LEFT
arrow. Press LEFT
arrow.
measure
exit
exit icon selected/highlighted
exit icon deselected
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 01/2014, A5E32221386-AB
arrow to
arrow to Zoom out.
arrow.