Dimension A (2.4.1.3.); Dimension L (2.4.1.4.); Xy Index (2.4.1.5.) - Siemens SITRANS L Operating Instructions Manual

Radar transmitters with profibus pa
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

7.3.4.4

Dimension A (2.4.1.3.)

Description
Values
Factory setting
Related parame-
ters
7.3.4.5

Dimension L (2.4.1.4.)

Description
Values
Factory setting
Related parame-
ters
7.3.4.6

XY index (2.4.1.5.)

Description
Level values
See Level unit (2.3.2.) (Page 93)
Volume values
See PV units (volume/level)
(2.3.3.) (Page 93)
Enter up to 11 level breakpoints, where the corresponding volume is known. The values
corresponding to 100% and 0% levels must be entered. The breakpoints can be ordered from
top to bottom, or the reverse.
Example (values are for example purposes only)
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
The height of the vessel bottom when the bottom is conical, pyramidal, parabol-
ic, spherical, or flat -sloped. If the vessel is horizontal with parabolic ends, the
depth of the end. For an illustration, refer to Vessel shape (2.4.1.1.) (Page 99).
0.0000 to 999999 mm in Level Units
0.0
Vessel shape (2.4.1.1.) (Page 99)
Length of the cylindrical section of a horizontal parabolic end vessel, in Level
Units. For an illustration, refer to Vessel shape (2.4.1.1.) (Page 99).
Range: 0.0000 to 999999 in Level Units
0.0
Vessel shape (2.4.1.1.) (Page 99)
If your vessel shape is more complex than any of the preconfig-
ured shapes, you can define the shape as a series of segments. A
value is assigned to each level breakpoint and a corresponding
value is assigned to each volume breakpoint. Volume values are
defined in volume units and can be percent or volumetric; level
values are defined in level units, and can be percent or linear.1)
Range: 0.0000 to 99999 (m, cm, mm, ft, in, %)
Factory setting: 0.0
Range: 0.0000 to 99999 (% or volumetric units)
Factory setting: 0.0
point no.
Break-
Level
value (m)
1
0
2
5
3
9
4
19.5
Parameter assignment
7.3 Setup (2.)
Volume
value (l)
0
500
3000
8000
101