Low calibration point (2.3.7.1.)
Description
Values
Factory setting
Related
parameters
① Sensor value
② Space
③ Distance
④ High calibration point
The point from which level measurement is referenced. Refer to Uni-construction
1)
polypropylene rod antenna (Page 154) and Flange adapter versions (Page 159).
High calibration point (2.3.7.2.)
Description
Values
Factory setting
Related parameters
Note
When setting the High Calibration Point value, note that echoes are ignored within Near
Range (2.5.1.)
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
Distance from sensor reference point
fined in Units.
0 to 20 m
20.00 m
Far range (2.5.2.) (Page 103)
Units (2.3.1.) (Page 93)
Distance from Sensor Reference to High Calibration Point (correspond-
ing to High Level Point). Unit is defined in Unit (2.3.1.).
0 to 20 m
0.000 m
Near range (2.5.1.) (Page 102)
Units (2.3.1.) (Page 93)
to Low Calibration Point. Units are de-
1)
⑤ Low calibration point
⑥ Far range
⑦ Level
Parameter assignment
7.3 Setup (2.)