The Gsd File; Bus Termination; Power Demands; Profibus Address - Siemens SITRANS L Operating Instructions Manual

Radar transmitters with profibus pa
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

E.4

The GSD file

The GSD file SIEM810F.gsd is available from the SITRANS LR200 product page on our
website.
www.siemens.com/LR200 (www.siemens.com/LR200) > downloads
E.5

Bus termination

Note
PROFIBUS PA cable shield MUST be terminated at both ends of the cable for it to work
properly. Please refer to the PROFIBUS PA User and Installation Guidelines (order number
2.092), available from:
www.profibus.com (www.profibus.com)
E.6

Power demands

To determine how many devices can be connected to a bus line, calculate the combined
maximum consumption of all the connected devices: 10.5 mA for each SITRANS LR200. Allow
a current reserve for safety.
E.7

PROFIBUS address

A unique PROFIBUS address identifies each device on the network.
• To set PROFIBUS address, see Device address (5.1.) (Page 136).
• To reset the PROFIBUS address to 126, see Master reset (4.1.) (Page 122).
Notes:
• It is possible to change the device address via a Class 1 master (for example, a PLC) and
lock the device address to prevent further changes.
• If this Address Lock is on, the PA address cannot be changed. This lock can be disabled
only by performing an Address Reset.
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
PROFIBUS communication
E.4 The GSD file
201

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lr200

Table of Contents