Parameter assignment
7.3 Setup (2.)
Sensor offset (2.3.7.3.)
Description
Values
Factory setting
Related parame-
ters
The value produced by the echo processing which represents the distance from sensor
reference point to the target. Refer to Calibration (2.3.7.) (Page 94) for an illustration.
Low level point (2.3.7.4.)
Description
Factory setting
High level point (2.3.7.5.)
Description
Factory setting
Level offset (2.3.7.6.)
Description
Factory setting
Antenna (2.3.7.7.)
Read only. Identifies antenna configuration (Near Range [blanking] distance is automatically
adjusted to suit).
96
Sensor Offset is a constant offset that can be added to or subtracted from sensor
value
to compensate if the sensor reference point has shifted. For example, this
1)
could result from adding a thicker gasket or reducing the standoff/nozzle height.
The units are defined in Units (2.3.1.) (Page 93).
-99.999 to +99.999
0.00
Units (2.3.1.) (Page 93)
The level when the material is at Low Calibration Point. The unit is defined in
Level units.
0%
The level when the material is at Low Calibration Point. The unit is defined in
Level units.
100%
A constant offset that can be added to Level. The unit is defined in Level units.
0%
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF