7.3.3.8

Rate (2.3.8.)

Response rate (2.3.8.1.)
Response Rate sets the reaction speed of the device to measurement changes. Use a setting
just faster than the maximum filling or emptying rate (whichever is greater).
Note
Changing Response Rate resets Fill rate/min (2.3.8.2.) (Page 97), Empty rate/min (2.3.8.3.)
(Page 98) and Filter time constant (2.6.8.1.) (Page 114).
Response rate
slow (factory set-
ting)
medium
fast
Fill rate/min (2.3.8.2.)
Fill rate defines the maximum rate at which the reported sensor value
increase. Allows you to adjust the device's response to increases in the actual material level.
Fill rate is automatically updated whenever Response rate (2.3.8.1.) (Page 97) is altered.
Note
Enter a value slightly greater than the maximum vessel-filling rate, in units per minute.
Response rate (2.3.8.1.) (Page 97)
Options
Range
Related
parameter
The value produced by the echo processing which represents the distance from sensor
1)
reference point to the target.
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
Fill rate/min (2.3.8.2.)
(Page 97)
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
slow (factory setting)
medium
fast
0 to 99999 m / min.
Level unit (2.3.2.) (Page 93)
Empty rate/min
(2.3.8.3.) (Page 98)
Fill rate (2.4.2.)
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
Parameter assignment
7.3 Setup (2.)
Filter time constant
(2.6.8.1.) (Page 114)
10 s
10 s
0 s
is allowed to
1)
97