6.3.4.2
Step 1 - Identification
Note
The layout of the dialog boxes shown may vary according to the resolution setting for your
computer monitor.
1. Click on Read Data from Device to upload Quick Start parameter settings from the device to
the PC/PG and ensure PDM is synchronized with the device.
2. If required, change the language for the local user interface.
3. Click on NEXT to accept the default values. (Description, Message, and Installation Date
fields can be left blank.)
6.3.4.3
Step 2 - Application
Select the application type (level or volume) and the material
See Application with Stillpipe (Page 64) for a Low Dielectric Liquid application.
1)
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
Operating
6.3 Remote operation
, then click on NEXT.
1)
59