Siemens SITRANS L Operating Instructions Manual page 109

Radar transmitters with profibus pa
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

To set Auto False Echo Suppression via SIMATIC PDM:
Open the menu Device – Echo Profile Utilities and click on the tab Auto False Echo
Suppression. For more detailed instructions, refer to Auto false echo suppression (Page 69).
To set Auto False Echo Suppression via the handheld programmer:
Options
3. Go to Auto false echo suppression range (2.5.10.2.) (Page 109) and enter the value
calculated in step 2.
4. Go to Auto false echo suppression (2.5.10.1.) (Page 107) and press RIGHT arrow to open
Edit Mode.
5. Select Learn. The device will automatically revert to On (use "Learned TVT") after a few
seconds.
Auto false echo suppression range (2.5.10.2.)
Description
Values
Factory setting
Related
parameters
1. Calculate range according to Auto false echo suppression (2.5.10.1.) (Page 107) steps 1)
and 2).
2. Press RIGHT arrow to open Edit mode.
3. Enter the new value and press RIGHT arrow to accept it.
4. Set Auto false echo suppression (2.5.10.1.) (Page 107).
Hover level (2.5.10.3.)
Description
Values
Factory setting
Note
When the device is located in the center of the vessel, the TVT hover level may be lowered to
increase the confidence level of the largest echo.
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF
OFF
Default TVT will be used
ON (factory setting)
'Learned' TVT will be used
LEARN
'Learn' the TVT
Specifies the range within which Learned TVT is used. For more detail, refer to
Auto false echo suppression (2.5.10.1.) (Page 107).
Range: 0.00 to 20.00 m
1.00 m
Units (2.3.1.) (Page 93)
Defines how high the TVT (Time Varying Threshold) is placed above the noise
floor of the echo profile, as a percentage of the difference between the peak of
the largest echo in the profile and the noise floor. Refer to Auto false echo sup-
pression (2.5.10.1.) (Page 107) for an illustration.
Range: 0 to 100%
40%
Parameter assignment
7.3 Setup (2.)
109

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lr200

Table of Contents