Commissioning
6.2 Operating via the handheld programmer
6.2.3.3

Requesting an Echo Profile

• In PROGRAM mode, navigate to: Level Meter > Diagnostics
(3.) > Echo Profile (3.1.)
• Press RIGHT arrow
● Use UP
becomes active.
● To move a cross-hair, press RIGHT
decrease.
● To Zoom into an area, position the intersection of the cross-hairs at the center of that area,
select Zoom, and press RIGHT
● To update the profile, select Measure and press RIGHT
● To return to the previous menu, select Exit then press RIGHT
70
to request a profile.
Confidence
Distance from Low Calibration Point to vertical cross-hair
Algorithm: tF (trueFirst)
Distance from flange face to target
Pan left/right - selected
Pan up/down
or DOWN
arrow to scroll to an icon. When an icon is highlighted, that feature
arrow to increase the value, LEFT
arrow. Press LEFT
arrow to Zoom out.
SITRANS LR250 (FOUNDATION FIELDBUS)
Operating Instructions, 08/2014, A5E32221411-AC
Zoom
Measure
Exit
Exit icon selected
Exit icon deselected
arrow to
arrow.
arrow.