Bosch ICP-CC408 Installation Manual page 70

Table of Contents

Advertisement

ICP-CC408 | Installation Guide | 16.0
0,9
Kiss-Off after Exit Time
This output operates after the first successful
transmission to the base station receiver when Exit
Time expires. The output is reset when the system is
disarmed.
0,11
Entry Warning
This output operates when during Entry Timer 1,
Entry Timer 2, or Entry Guard Timer for STAY
Mode. The output is reset when the Entry Time
expires.
0,12
Entry Warning + Day Alarm Resetting
This output combines Entry Warning and Day Alarm
Resetting so that either of these two events activates
the output.
If the output is activated by Entry Timer 1, Entry
Timer 2, or Entry Guard Timer for STAY Mode, the
output is reset when the Entry Time expires or the
system is disarmed.
If a zone programmed for Day Alarm is activated
when the system is disarmed, the output is reset
when the zone is resealed. You can turn Day Alarm
on and off by holding down [4]. Refer to Section 14.1
Day Alarm Information on page 56 for programming
zones to operate for Day Alarm.
0,13
Exit Warning + Entry Warning + Day Alarm
Resetting
This output operates when the system is armed,
regardless of whether zones are sealed or unsealed,
until Exit Time expires.
The output operates again during Entry Time and is
reset when Entry Time expires or the system is
disarmed.
The output also operates during the Entry Guard
Timer for STAY Mode time.
If a zone programmed for day alarm is activated
when the system is disarmed, the output is reset
when the zone is resealed. You can turn Day Alarm
on and off by holding down [4]. Refer to Section 14.1
Day Alarm Information on page 56 for programming
zones to operate for Day Alarm.
0,14
Day Alarm Resetting
This output operates when a zone programmed for
Day Alarm is activated. The output is reset when the
Day Alarm zone is resealed. You can turn Day
Alarm on and off by holding down [4]. Refer to
Section 14.1 Day Alarm Information on page 56 for
programming zones to operate for Day Alarm.
0,15
Day Alarm Latching
This output operates when a zone programmed for
Day Alarm is activated. The output is reset by
pressing [AWAY]. You can turn Day Alarm on and
off by holding down [4]. Refer to Section 14.1 Day
Alarm Information on page 56 for programming zones
to operate for Day Alarm.
Bosch Security Systems, Inc. | 12/08 | F01U089463-02
Programmable Outputs
1,0
Day Alarm Enabled
This output operates when Day Alarm is enabled.
The output is reset when Day Alarm is turned off.
Refer to Section 14.1 Day Alarm Information on page 56
for programming zones to operate for Day Alarm.
You can turn Day Alarm on and off by holding
down [4]. Three beeps indicate that Day Alarm is
turned on, two beeps indicate that Day Alarm is
turned off. Refer to Section 6.4.7 Turning Day Alarm On
and Off on page 40 for more information.
1,1
Telephone Line Fail
This output operates when the built-in telephone line
fault module detects that the telephone line is
disconnected longer than 40 sec. The output is reset
when the telephone line is restored continuously for
longer than 40 sec. This output does not operate
unless Option 1 in Location 176 is selected (refer to
Section 11.11 Telephone Line Fault Options on page 49).
1,2
Kiss-Off Received
This output operates after the control panel
successfully transmitted to the receiving party.
1,3
AUX Power Supply
This output operates when either the 1 A codepad
AUX power supply
fails. The output is reset when the faulty
supply
power supply
1,4
AC Fail
This output operates when the AC MAINS fails. The
output is reset when the AC MAINS is restored. This
output operates regardless of whether Option 2 in
Location 426 is selected (refer to Section 18.3 System
Options 3 on page 79).
1,5
Low Battery
This output operates when a Dynamic Battery Test
detects the battery failed or the battery voltage is
below 11.5 VDC. The Dynamic Battery Test is
performed every 4 hours after the system is powered
up and every time the system is armed.
This output is reset only after a Dynamic Battery Test
reports that the backup battery voltage is normal.
1,6
Horn Speaker Monitor Fail
If the Enable Monitoring of Horn Speaker option (2)
in Location 424 is selected (refer to Section 18.1 System
Options 1 on page 78), this output operates when the
horn speaker is disconnected. The output is reset
when the horn speaker is reconnected.
1,7
Sensor Watch Alarm
This output operates when the Sensor Watch Count
is reached. Refer to Section 14.3.5 Zone Options 1 on
page 60 for more information on programming zones
for sensor watch. Refer to Section 17.7 Sensor Watch
Time on page 76 for setting the number of days
before a zone registers as a faulty sensor watch zone.
Fail
or the 1 A accessories
is reset.
EN | 70