• Each AC power supply has one AC appliance inlet. Each inlet requires a dedicated AC power feed
and a dedicated customer site circuit breaker. We recommend that you use a dedicated circuit
breaker rated at 20 A (100 VAC) or 16 A (240 VAC), or as required by local code.
WARNING: The router is pluggable type A equipment installed in a restricted-access
location.
• The power cord serves as the main disconnecting device for the AC-powered device. The socket
outlet must be near the AC-powered device and be easily accessible.
• The cores in the main lead are colored in accordance with the following code:
• Green or yellow—Earth (label: G)
• White or blue—Neutral (label: N)
• Brown or black—Live (label: L)
• When a router is equipped with two AC power supplies, both power cords (one for each power
supply) must be unplugged to completely disconnect power to the router.
WARNING: The attached power cable is only for this product. Do not use the cable for
another product. Japanese translation:
RELATED DOCUMENTATION
ACX500 Power Overview | 68
ACX500 DC Power Electrical Safety Guidelines | 239
ACX500 AC Power Electrical Safety Guidelines | 237
ACX500 DC Power Specifications | 73
ACX500 AC Power Specifications | 69
238