Service Settings - Trane IntelliPak with Symbio 800 Programming Manual

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

Service Settings

Provides access to low level parameters required for all unit functionality.
Table 17. Service settings
Value
Power-Up Start Delay
VAV Box Stroke Time
Duct Static Press High Limit Setpoint 4.00 IWC (1.20-5.70)
Low Ambient Lockout Setpoint
Duct Static Press High Limit Protection Enable (Disable, Enable)
Design Air Flow
Local Atmospheric Pressure
Relief Fan Maximum Speed Setpoint
Supply Fan Bypass Mode Enabled
Bypass Duct Static Diff. Pressure
Occupied Bypass Time
Occupied Offset
Occupied Standby Offset
Cooling Design Delta Temp
Temp. Control Softload Time Cooling
Duct Static Pressure Softload Time
Occupied Dehumidification Offset
Unoccupied Dehumidification Offset
Purge Reheat Coil Interval Setting
Temp Control Softloading Time Heating 120 Sec (0-1800)
Occupied Space Cool Air Flow Cmd
Compensation
Suction Superheat Setpoint
Suction Superheat Tracking Time
RT-SVP011E-EN
Factory Default (Range)
0 Sec (0-300)
6 Min (1-10)
Configuration Dependent
Configuration Dependent
14.7 PSIA (10-16)
200 RPM (100-5000)
Off (Off, On)
0.3 IWC (0.3-2.0)
120 Min (0-240)
1.5 °F (1-30)
7.5 °F (1-30)
20 °F (5.0-40.0)
120 Sec (0-1800)
30 Sec (0-1800)
10.0% (5.0-15.0)
10.0% (5.0-15.0)
120 Min (60-480)
0.0% (-20.0-100.0)
12.6 °F (9.0-27.0)
20.0 Sec (0.0-200.0)
TD7 Display
Description
Used to delay unit operation after a
power cycle or after the termination of
all VOM/EOM events.
Used to manage unit airflow with VAV
system delays.
Inhibits supply fan if duct pressure
exceeds this setpoint.
Inhibits compressor operation if
outdoor air temperature drops below
this value.
Disable this protection during active
supply fan bypass mode. Always
enabled in non-bypass mode.
Contact Trane Technical Support.
This entry should reflect the average
pressure expected at the unit's
geographical elevation.
This speed entry should reflect the
maximum design relief airflow for the
given application.
Used to place the unit's supply fan
VFD(s) into bypass mode.
Contact Trane Technical Support.
The amount of time that will expire
before a unit will return to unoccupied
mode after entering bypass.
This entry establishes a deadband
between occupied space heating and
space cooling setpoints.
This entry establishes a deadband
between occupied standby space
heating and space cooling setpoints.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Occupied dehumidification terminates
when space humidity falls below
occupied dehumid setpoint minus this
value.
Unoccupied dehumidification
terminates when space humidity falls
below unoccupied dehumid setpoint
minus this value.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
47