Unit Settings - Trane IntelliPak with Symbio 800 Programming Manual

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

Unit Settings

Unit Settings are the basic parameters for unit operation and provide the default values for
setpoints and unit operating modes.
Table 16. Unit settings value
Value
Arbitration Method
Supply Fan Configuration
Cmd Default
Heat Cool Mode Request
Default (Single zone units)
Heat Cool Mode Request
Default (Multi zone units)
Discharge Air Cooling
Setpoint Default
Discharge Air Heating
Setpoint Default
Duct Static Pressure Setpoint
Default
Occupied Cooling Setpoint
Default
Occupied Heating Setpoint
Default
Space Dehumidification
Setpoint Default
Unoccupied Cooling Setpoint 85.0°F (40.0 - 115.0)
Unoccupied Heating Setpoint 60.0°F (40.0 - 115.0)
Space dehumidification
Unoccupied Setpoint Default
Pre cool Setpoint
Morning Warmup Setpoint
Daytime Warmup Setpoint
Occupied Standby Cooling
Setpoint Default
Occupied Standby Heating
Setpoint Default
Occupancy Input Default
Economizer Min. Position
Setpoint Default
Reference Enthalpy Setpoint 25.0 BTU/lbm (19.0 - 36.0)
RT-SVP011E-EN
Default (range)
Full Source (Full Source, Local
Source, Default Source)
Continuous (Cycling, Continuous) Supply fan configuration.
Auto (Heat, Cool, Off, Auto)
Heat (Heat, Cool, Off)
55.0°F (40.0 - 75.0)
100.0°F (50.0 - 120.0)
2.00 IWC (0.05 - 5.10)
74.0°F (40.0 - 115.0)
71.0°F (40.0 - 115.0)
60.0% (40.0 - 65.0)
60.0% (40.0 - 65.0)
74.0°F (40.0 - 83.0)
72.0°F (50.0 - 90.0)
72.0°F (50.0 - 90.0)
78.0°F (40.0 - 115.0)
67.0°F (40.0 - 115.0)
Occupied (Occupied, Unoccupied) Occupancy input default value.
25.0% (0.0 - 100.0)
Description
Full source-Result of arbitration from external
®
controls (For example: Tracer
party system control).
Local source-Isolates unit setpoints, settings, and
sensors to local wired or wireless sources. Removes
Full Sources.
Default Source-Isolates unit to TD7 Display
setpoints and settings, and local sensors. Removes
Local Source and Full Sources.
Default Heat Cool Mode Input for Single Zone VAV
and Constant Volume Zone Temperature units.
Default Heat Cool Mode Input for Multi Zone VAV
and Constant Volume Discharge Air Temperature
units.
Discharge air cooling setpoint.
Discharge air heating setpoint.
Duct static pressure setpoint default.
Space temperature occupied cooling setpoint.
Space temperature occupied heating setpoint.
Space dehumidification enable setpoint in occupied
modes.
Space temperature unoccupied cooling setpoint.
Space temperature unoccupied heating setpoint.
Space dehumidification enable setpoint in
unoccupied mode.
Defines the space temperature above which pre-
cool will be exercised, when enabled.
Defines the space temperature below which
morning warmup will be exercised, when enabled.
Space temperature below which daytime warmup
will be enabled.
Space temperature occupied standby cooling
setpoint.
Space temperature occupied standby heating
setpoint.
Economizer damper minimum position setpoint.
Related to the economizer enable decision, this
default value determines the outdoor air enthalpy
below which economizing is enabled.
TD7 Display
SC+, TGP2, 3rd
45