Trane IntelliPak with Symbio 800 Programming Manual page 85

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

Diagnostics
Target
Comm Loss: Mixed Air
Temperature
[Single Evap]
DX Cooling
Comm Loss: Mixed Air
Temperature EvapX
[Spilt Evap]
X = "A" or "B"
Comm Loss: Outdoor
Unit
Air Damper Feedback
Comm Loss: Outdoor
Unit
Air Humidity
Comm Loss: Outdoor
DX Cooling
Air Temperature
Comm Loss: Outdoor
Unit
Airflow Pressure
Comm Loss: Power
Unit
Meter
Comm Loss: Pre Filter
Unit
Pressure Sensor
Comm Loss: Relief Air
Unit
Damper
Comm Loss: Relief Air
Unit
Damper Feedback
RT-SVP011E-EN
Severity
Persistence
Normal
Non-Latching
Shutdown
Warning
Non- Latching
Warning
Non-Latching
Warning
Non-Latching
Warning
Non-Latching
Warning
Non-Latching
Warning
Non-Latching
Warning
Non- Latching
Warning
Non- Latching
Condition / Response
Continual loss of communication between the
Symbio™ 800 and the LLID/Hex IO has occurred for
a 30 second period.
Units with Single Evap: Rapid Restart economizer
cooling is not allowed.
Units with Split Evap: These units average the two
sensors to create an estimated Mixed Air
Temperature.
Temp X failed with the other sensor available: Rapid
Restart economizer cooling is allowed.
Temp X failed with the other sensor not-available:
Rapid Restart economizer cooling is not allowed.
Continual loss of communication between the
Symbio™ 800 and the LLID/Hex IO has occurred for
a 30 second period.
Outdoor air damper is commanded closed and
economizer operation is disabled.
Continual loss of communication between the
Symbio™ 800 and the LLID/Hex IO has occurred for
a 30 - 35 second period.
This drives a 'fall back' response to Economizer
enthalpy decision.
Continual loss of communication between the
Symbio™ 800 and the LLID/Hex IO has occurred for
a 30 second period.
Economizing is disabled. All DX operation is inhibited.
Continual loss of communication between the
Symbio™ 800 and the LLID/Hex IO has occurred for
a 30 second period.
Traq air flow control is inhibited and the unit will fall
back to alternate minimum ventilation control.
Continual loss of communication between the
Symbio™ 800 and the MODBUS
meter) has occurred for a 30 second period.
No unit response.
Continual loss of communication between the
Symbio™ 800 and the LLID/Hex IO has occurred for
a 30 second period.
No unit response.
Continual loss of communication between the
Symbio™ 800 and the LLID/Hex IO has occurred for
a 30 second period.
Unit will command the damper closed and disable
Statitrac control.
Continual loss of communication between the
Symbio™ 800 and the LLID/Hex IO has occurred for
a 30 second period.
Unit will command the damper closed and disable
Statitrac control.
Troubleshooting
Reset Level
Remote
Remote
Remote
Remote
Remote
®
Server (power
Remote
Remote
Unit
Unit
85