Trane IntelliPak with Symbio 800 Programming Manual page 91

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

Diagnostics
Target
Heat Inducer High
Press Manf X Server
Heat
where X is "1" or "2"
Heat Inducer Low Press
Manf X Server
Heat
where X is "1" or "2"
Heat Invalid ID Chip
Heat
Manf 1 Server
Heat Open Fuse Manf X
Server
Heat
where X is "1" or "2"
Heat Primary Limit
Heat
Open Manf 1 Server
Heat Supply Air Flow
Proving Lockout Manuf
Heat
X
where X is "1" or "2
High Compressor Press
Diff Lockout CktX
Circuit
where X is "1" or "2"
High Compressor Press
Differential CktX
Circuit
where X is "1" or "2"
RT-SVP011E-EN
Severity
Persistence
Warning
Non-Latching
Warning
Non-Latching
Warning
Non-Latching
Warning
Non-Latching
Warning
Non-Latching
Warning
Non- Latching
Immediate
Latching
Shutdown
Immediate
Non -Latching
Shutdown
Condition / Response
A 'Heat Inducer High Press Manf X' condition has
occurred on the 1285's own MODBUS
board on the first manifold.
Staged Gas Heat control boards only.
Does not lock out any burners associated with the
first heat control board on the manifold.
A 'Heat Inducer Low Press Manf X' condition has
occurred on the 1285's own MODBUS
board on the first manifold.
Staged Gas Heat control boards only.
Does not lock out any burners associated with the
first heat control board on the manifold.
An invalid id chip condition has condition has
occurred on the 1285's own MODBUS
board on the first manifold.
Does not lock out any burners associated with the
first heat control board on the manifold.
Staged Gas Heat control boards only.
Note: If the incorrect ID chip is inserted into the board
simply based off of the current configuration, the
first heat control board will display this as a comm
loss coming from its server board.
An open fuse condition has condition has occurred on
®
the 1285's own MODBUS
server control board on
the first manifold.
Staged Gas Heat control boards only.
Does not lock out any burners associated with the
first heat control board on the manifold.
A primary limit condition has condition has occurred
for an extended duration on the 1285's own
®
MODBUS
server control board on the first manifold.
Staged Gas Heat control boards only.
Does not lock out any burners associated with the
first heat control board on the manifold.
The Air Flow Proving circuit is open, while a Firing
Rate Demand is requested. This could be open on the
board connector.
Modulating Gas Heat control boards only.
All burners on the manifold are unavailable. Will allow
another retry in between 30 seconds to 5 minutes.
Compressor involute pressure differential exceeded
allowable limits.
Circuit X is inhibited.
Compressor involute pressure differential exceeded
allowable limits.
Circuit X is inhibited.
Troubleshooting
Reset Level
®
server control
Remote
®
server control
Remote
®
server control
Remote
Remote
Remote
Remote
Remote
Remote
91