Table 19. Feature settings value (continued)
Value
Timed Override Request Wireless
Enable
System Mode Wireless Enable
Space Temp Cooling Setpoint
Wireless Enable
Space Temp Heating Setpoint
Wireless Enable
Supply Fan Config Cmd Wireless
Enable
Space Temperature Wireless
Enable
Space Humidity Wireless Enable Enable (Disable, Enable)
Space Static Pressure Wireless
Enable
Space CO
Wireless Enable
Superheat High Limit Lockout
Enable

Discharge Air Reset

This button allows edits to Discharge Air Cooling Reset and Discharge Air Heating Rest functions.
Settings are provided in table below.
Table 20. Discharge air reset value
Value
Discharge Air Cooling Reset
Outdoor Air Cooling Reset Start
Outdoor Air Cooling Reset End
Outdoor Air Cooling Reset Amount
Max.
Zone Cooling Reset Start Temp.
Zone Cooling Reset End Temp.
Zone Cooling Reset Amount Max 5.0°F (0 - 20.0)
Discharge Air Heating Reset
Outdoor Air Heating Reset Start 32.0°F (0 - 59.0)
Outdoor Air Heating Reset End
Outdoor Air Heating Reset
Amount Max.
Zone Heating Reset Start Temp. 69.0°F (50.0 - 71.0)
Zone Heating Reset End Temp.
56
Range (default)
Enable (Disable, Enable)
Enable (Disable, Enable)
Enable (Disable, Enable)
Enable (Disable, Enable)
Enable (Disable, Enable)
Enable (Disable, Enable)
Enable (Disable, Enable)
Concentration
2
Disable (Disable, Enable) Disabled by default when wireless is installed.
Enable (Disable, Enable)
Range (default)
None (None, Outdoor
Air, Zone)
90.0°F (71.0 - 95.0)
70.0°F (0 - 89.0)
5.0°F (0 - 20.0)
72.0°F (70.0 - 90.0)
69.0°F (50.0 - 71.0)
None (None, Outdoor
Air, Zone)
60.0°F (33.0 - 95.0)
5.0 °F (0 - 20.0)
72.0°F (70.0 - 90.0)
Description
Enabled by default when wireless is installed.
Enabled by default when wireless is installed.
Enabled by default when wireless is installed.
Enabled by default when wireless is installed.
Enabled by default when wireless is installed.
Enabled by default when wireless is installed.
Enabled by default when wireless is installed.
Enabled by default when wireless is installed.
Enabled by default.
Description
Selects the type of Discharge Air Cooling Reset to be
performed by controller. None, disables the function.
Starting outdoor air temperature at which discharge air
cooling setpoint will begin reset.
Ending outdoor air temperature at which discharge air
cooling setpoint will reset.
The amount the discharge air cooling setpoint will increase
over the specified range.
Starting space temperature at which discharge air cooling
setpoint will begin reset.
Ending space temperature at which discharge air cooling
setpoint will reset.
The amount the discharge air cooling setpoint will increase
over the specified range.
Selects the type of Discharge Air Heating Reset to be
performed by controller. None, disables the function.
Starting outdoor air temperature at which discharge air
Heating setpoint will begin reset.
Ending outdoor air temperature at which discharge air
Heating setpoint will reset.
The amount the discharge air Heating setpoint will decrease
over the specified range.
Starting space temperature at which discharge air Heating
setpoint will begin reset.
Ending space temperature at which discharge air Heating
setpoint will reset.