Table 8.
Unit
Morning Warm Up
Night Purge
Pre Cool
Ventilation Override Mode X
Note: All Running Sub Modes are actual operating states of the control and algorithms.
Circuit Operating Modes
The tables below show each circuit - top level mode and lists the sub modes possible
Table 9.
Circuit
Top Level Mode
Stopped
Stopped Sub Modes
Diagnostic Shutdown – Manual
Reset
Front Panel Circuit Lockout
Table 10. Circuit operation-top level mode - run inhibit
Circuit
Top Level Mode
Run Inhibit
Run Inhibit Sub Modes
Diagnostic Shutdown – Auto Reset The circuit has been shutdown on a diagnostic that may clear automatically.
No Compressors Available
Start Inhibited by Low Suction
Pressure
Running Inhibited by Frost
Protection
Table 11. Circuit operation-top level mode - auto
Circuit
Top Level Mode
Auto
Auto Sub Modes
Calibrating EXV
RT-SVP011E-EN
Unit operation - top level mode - running (continued)
Circuit operation-top level mode - stopped
Description
The circuit is not running, and cannot run without intervention.
Description
The circuit has been shutdown on a latching diagnostic.
The circuit is manually locked out by Manual Override Control at the Front Panel.
Unlike other Manual Overrides these locks are not terminated when the Manual
Overrides Time expires, and are persisted through power cycles.They can only be
cleared at the Front Panel.
Description
The given circuit is currently being inhibited from starting (and running), but may
be allowed to start if the inhibiting or diagnostic condition is cleared.
All compressors on the circuit are currently locked out and unable to start.
The suction pressure dropped below a pressure threshold. See the IOM for more
details.
Compressors on the circuit are inhibited to remove frost on the coil.
Description
The circuit is not currently running but can be expected to start at any moment
given that the proper conditions are satisfied.
The EXVs are performing a calibration cycle. A calibration is performed whenever
the unit controller is power cycled, or when the unit controller is running, the
circuit is off, and it has been at least EXV Recalibration Time since the last EXV
Calibration was executed.
Description
Morning Warm Up is active. Morning Warmup Active = True
Night Purge mode is active. Heat Cool Mode Request =
Night Purge and Occupancy Status = Occupied
Pre Cool Active = True
Ventilation Override Mode is active. Where X = A, B, C, D,
or E
TD7 Display
37