Table 17. Service settings (continued)
Value
Rapid Restart Minimum Percent
Capacity
Rapid Restart Control Band Setting
Rapid Restart Mixed Air Temp. Low
Limit
External Heat Supply Fan Speed
Setpoint
Electrical Service Type Command
Outdoor Air Damper Min. Voltage
Outdoor Air Damper Max. Voltage
Outdoor Air Damper Direct/Reverse
Acting
Outdoor Air Damper Stroke Time
Relief Air Damper Min. Voltage
Relief Air Damper Max. Voltage
Relief Air Damper Direct/Reverse
Acting
Relief Air Damper Stroke Time
Condenser Reheat Valve Min. Position
Setpoint
Condenser Reheat Valve Max. Position
Setpoint
Condenser Cooling Valve Min. Position
Setpoint
Condenser Cooling Valve Max. Position
Setpoint
Duct Static Pressure Control Prop Gain 13.2 (0.1-1000.0)
Duct Static Pressure Control Integral
Time
Duct Static Pressure Deadband
Space Static Pressure Control Prop
Gain
Space Static Pressure Integral Time
Space Static Pressure Control
Deadband
RT-SVP011E-EN
Factory Default (Range)
25.0% (20.0-100)
20.0°F (5.0-40.0)
42.0°F (40.0-55.0)
100.0% (0.0-100.0)
Wye (Delta, Wye)
2.0 V (0.0-9.9)
10.0 V (2.1-10.0)
Direct (Direct, Reverse)
30 Sec (1-255)
2.0 V (0.0-9.9)
10.0 V (2.1-10.0)
Direct (Direct, Reverse)
30 Sec (1-255)
15.0% (10.0-35.0)
85.0% (40-100.0)
15.0% (10.0-35.0)
85.0% (40-100.0)
5 Sec (0-3600)
0.50 IWC (0.00-4.01)
24.0 (0.5-500.0)
2.0 Sec (0.1-1000.0)
0.04 IWC (0.02-0.40)
TD7 Display
Description
Used to set the minimum compressor
stage regardless of Critical Temp
Setpoint target needs.
Contact Trane Technical Support.
Contact Trane Technical Support.
Sets the minimum supply fan speed for
single zone heating. Higher speeds are
allowed.
Used to identify the applied 3-phase
power connection to the unit for power
meter applications.
Minimum voltage setting for the
applied damper actuator equating to
fully closed.
Maximum voltage setting for the
applied damper actuator equating to
fully open.
Sets damper position (P) stroke
direction. Does Pmin  Pmax equate to
Vmin  Vmax, or Vmax  Vmin.
The time it takes for the actuator to
stroke from Pmin to Pmax.
Minimum voltage setting for the
applied damper actuator equating to
fully closed.
Maximum voltage setting for the
applied damper actuator equating to
fully open.
Sets damper position (P) stroke
direction. Does Pmin  Pmax equate to
Vmin  Vmax, or Vmax  Vmin.
The time it takes for the actuator
position (P) to stroke from Pmin to
Pmax.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
DB. Control deadband around the
static pressure setpoint. Control band
is Stp+1/2DB to Stp-1/2DB.
Contact Trane Technical Support.
Contact Trane Technical Support.
DB. Control deadband around the
static pressure setpoint. Control band
is Stp+1/2DB to Stp-1/2DB.
49