Arbitration Method; Feature Settings - Trane IntelliPak with Symbio 800 Programming Manual

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

Arbitration Method

Allows selection of the active source of setpoints and settings:

Feature Settings

Features Settings allows you to enable or disable features and functions.
Table 19. Feature settings value
Value
Economizer Airside Enable Default
Economizer Control Fallback
Balanced Compressor Staging
Traq Enable
Outdoor Air Flow Compensation
Enable
Demand Control Ventilation
Enable
Pre Cool Enable Command
Morning Warmup Enable
Command
Daytime Warmup Enable
Command
Dehumdification Enable
Command
Occupied Dehumidification Enable Enable (Disable, Enable)
Unoccupied Dehumidification
Enable
Unoccupied Cooling Mechanical
Enable
Unoccupied Cooling Economizing
Enable
Unoccupied Heating Enable
Loss of Charge Detection
Hot Gas Bypass
Condenser Reheat Enable
Supply Air Tempering Enable
Rapid Restart Enable
Rapid Restart Economizer Enable Enable (Disable, Enable)
Occupancy Input Wireless Enable Enable (Disable, Enable)
RT-SVP011E-EN
• Full Source – Result of arbitration from external controls (For example: Tracer
rd
3
party system control).
• Local Source – Isolates unit setpoints, settings, and sensors to local wired or wireless
sources. Removes Full Sources.
• Default Source – Isolates unit to TD7 Display setpoints and settings, and local sensors.
Removes Local Source and Full Sources.
Range (default)
Description
Auto, the controller uses sensor values and setpoints to
Auto (Disable, Enable,
enable and disable economizer operation. Enable,
Auto)
economizer operate as first stage of cooling. Disable,
disables economizer operation.
Reference Enthalpy (Dry
When Economizer with Comparative Enthalpy is
Bulb, Reference Enthalpy,
configured, control will fall back to Reference Enthalpy
Comparative Enthalpy)
in the event of a failure.
Disable (Disable, Enable) Disabled by default.
Enable (Disable, Enable)
Enabled when unit is configured for Traq.
Enable (Disable, Enable)
Enabled when variable speed fan configured.
Enable (Disable, Enable)
Enabled when configured.
Enable (Disable, Enable)
Enabled by default.
Enable (Disable, Enable)
Enabled when heat configured.
Enable (Disable, Enable)
Enabled when heat configured.
Enable (Disable, Enable)
Enabled when reheat is configured.
Enabled when reheat is configured.
Enable (Disable, Enable)
Enabled when reheat is configured.
Enable (Disable, Enable)
Enabled by default.
Enable (Disable, Enable)
Enabled by default.
Enable (Disable, Enable)
Enabled when heat configured.
Enable (Disable, Enable)
Enabled by default.
Enable (Disable, Enable)
When configured.
Enable (Disable, Enable)
When hot gas reheat is configured.
Disable (Disable, Enable) When Rapid Restart is configured.
Enable (Disable, Enable)
When Rapid Restart is configured.
When Rapid Restart is configured.
Enabled by default when wireless is installed.
TD7 Display
®
SC+, TGP2,
55