Trane IntelliPak with Symbio 800 Programming Manual page 46

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

TD7 Display
Table 16. Unit settings value (continued)
Value
Econ Enable Min. Outdoor Air
Temp Setpoint
Outdoor Air Min. Flow
Setpoint Default
Relief Enable Position
Setpoint
Space Static Pressure
Setpoint Default
Design Min. OA Damper
Position Setpoint Min Fan
Design Min. OA Damper
Position Setpoint Mid Fan
Design Min. OA Damper
Position Setpoint Max Fan
DCV Min. Outdoor Air Damper
Position at Min Fan
DCV Min. Outdoor Air Damper
Position at Max Fan
Design Min. Outdoor Air Flow
Setpoint
DCV Min. Outdoor Air Flow
Setpoint
Design CO
Design Min. OA Damper
Position Setpoint
DCV Min. Outdoor Air Damper
Position Setpoint
DCV CO
Demand Limit Setpoint
Default
Cooling Capacity Enable
Default
Heat Primary Enable Default 100.0% (0 - 100.0)
Evap Leaving Air Temp
Setpoint Default
Manual Overrides Timer
Setpoint
(a) Ranges are dynamically calculated based on the other setpoint ranges.
46
Default (range)
75°F (50.0 - 140.0)
2199 cfm (0 - 60000.0)
25.0 (0 – 100)
0.08 (-0.2 – 3.0)
25.0 (21.0 – 100.0)
20.0 (16.0 – 24.0)
15.0 (0.0 – 19.0)
15.0 (15.0 – 100)
5.0 (0 – 5.0)
6000.0 (2998.0 – 60000.0)
2000.0 (0 – 5002.0)
Setpoint
1000.0 ppm (500.0 - 2000.0)
2
15.0% (15.0 - 100.0)
5.0% (0 - 5.0)
Setpoint
400.0 ppm (50.0 - 900.0)
2
100.0% (0 - 100.0)
100.0% (0 - 100.0)
50.0°F (40.0 - 55.0)
1 Hr (1 - 78)
Description
Related to the economizer enable decision, this
default value determines the outdoor air
temperature below which economizing is enabled.
Default requested minimum outdoor air flow
setpoint.
Default setpoint to enable relief/exhaust fan
operation, based on outdoor air damper position.
Space static pressure setpoint default value.
Outdoor air flow compensation setpoint that
(a)
specifies the outdoor air damper position when
supply fan is at minimum speed.
Outdoor air flow compensation setpoint that
(a)
specifies the outdoor air damper position when
supply fan is at mid-point of speed range.
Outdoor air flow compensation setpoint that
(a)
specifies the outdoor air damper position when
supply fan is at maximum speed.
Outdoor air flow compensation with DCV, damper
(a)
position setpoint when supply fan at minimum
speed and space CO
Outdoor air flow compensation with DCV, damper
(a)
position setpoint when supply fan at maximum
speed and space CO
Outdoor air flow control (Traq) with DCV, air flow
(a)
setpoint when space at Design CO
limit).
Outdoor air flow control (Traq) with DCV, air flow
(a)
setpoint when space at DCV CO
limit).
Space design CO
Outdoor air minimum position control with DCV,
damper position setpoint when space at design CO
setpoint (high limit).
Outdoor air minimum position control with DCV,
damper position setpoint when space at DCV CO
setpoint (low limit).
Space Demand Control Ventilation CO
setpoint.
Demand limit setpoint default value. This value is
normally provided by the BMS to demand limit the
unit.
Cooling capacity enable default value. This value is
normally provided by the BMS to demand limit the
cooling capacity.
Heat primary capacity enable default value. This
value is normally provided by the BMS to demand
limit the heating capacity.
Dehumidification modes of operation, evaporator
leaving air temperature setpoint.
Sets the amount of time Manual Overrides are
allowed to be active. Timer resets when an override
is applied.
at DCV setpoint (low limit).
2
at DCV setpoint (low limit).
2
Setpoint (high
2
Setpoint (low
2
high limit setpoint.
2
low limit
2
RT-SVP011E-EN
2
2