to a timed override. For example, after the daily schedule ends at 12:00 am (midnight), the schedule
releases control over to the next event.

Creating a Schedule

Symbio™ UI leads you through the process of creating a schedule for your Symbio™ 800. If you
need help completing the steps, click the help icon located on each page. You can create a schedule
to control the following points and applications based on time and date:
Points and applications are referred to as members when they are assigned to a schedule.
Members can be assigned to only one schedule during the same effective period. Members must
be the correct type; that is, a binary point cannot be included in an analog schedule.
To create a schedule:
1. Click the create schedule button. The Create Schedule—Schedule Information page appears.
2. Enter a name for the schedule, and select the schedule type and effective dates.
3. Click next to continue. The Create Schedule—Select Members page appears.
4. From the selection tree, select members (spaces and areas) for the schedule, then click Add to
5. Click next to continue. The Create Schedule – Schedule Times page appears.
6. Select a schedule default. Each day is independent of the others and always begins with the
7. Add events to the schedule: click add event, which opens the event dialog box.
8. Enter a time for when the event will start and select a value.
9. Select the days of the week to which the event will be applied.
10. Click Add. The event appears in the schedule viewer. (To edit or delete an event, click on the
11. Click next to continue. The Create Schedule – Summary page appears.
12. Review the schedule. Click finish to save the new scheduled as summarized.

Alarm Configuration

In Symbio™ UI left navigation pane, select Alarm Configuration. From the Alarm Configuration
screen, you can view and edit alarm categories, alarm message templates, notification classes,
routing alarm email, and audible alarm notification.
RT-SVP011E-EN
Binary outputs and values
Analog outputs and values
Multistate outputs and values
move to selected items.
schedule default value. The schedule default value is applied to each day of the week and is the
value that the schedule defaults to at 12:00 a.m. for any given day.
event in the schedule viewer.)
Symbio™ UI