Dimensions and Weights

Service Clearances

Figure 3.
Service clearances for indoor units
Table 1.
Service clearance dimensions (inches) for indoor units
Component
A
Filter
B
Coil Pull
C
Fan Access, horizontal unit (motor side)
C
Fan Access, vertical unit (motor side)
C
Fan Access, vert unit with MI fan (motor side)
D
Control Box
E
VFD
F
EH
G Access Door - Access Section
Note: At a minimum, the above clearance dimensions are recommended on one side of the unit for regular service and maintenance. Clearances are mirrored to other side for
units with doors both sides. Refer to as-built submittal for locations of items such as filter access doors, coil, piping connections, motor locations, etc. Sufficient clearance
must be provided on all sides of unit for removal of access panels, plug panels, or section-to-section attachment brackets. Clearance for starters, VFDs, or other high-voltage
devices must be provided per NEC requirements.
CLCH-SVX009L-EN
F
Coil
Electric
Fan
Heat
VFD
Control Box
E
D
C
B
3
40.00
49.00
48.00
48.00
48.00
56.00
48.00
48.00
15.00
Unit
Coil/Access
Filter
Coil
G
A
B
Unit Size
6
8
10
12
44.00
42.00
42.00
40.00
62.00
66.00
78.00
86.00
48.00
48.00
51.00
54.00
48.00
48.00
51.00
54.00
48.00
48.00
51.00
54.00
56.00
56.00
56.00
56.00
48.00
48.00
48.00
48.00
48.00
48.00
48.00
48.00
15.00
15.00
15.00
15.00
Mixing Box / Filter
A
14
17
21
45.00
45.00
45.00
51.00
86.00
94.00
94.00
96.00
58.00
61.00
61.00
66.00
58.00
61.00
61.00
58.00
61.00
61.00
66.00
56.00
56.00
56.00
56.00
48.00
48.00
48.00
48.00
48.00
48.00
48.00
48.00
15.00
15.00
15.00
15.00
25
30
51.00
109.00
66.00
66.00
56.00
48.00
48.00
15.00
15