Trane IntelliPak with Symbio 800 Programming Manual page 59

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

Table 22. Complete list of manual override selections – circuit 1 or circuit 2 button
(a) Circuit and Compressor Lockouts will not be terminated when the Manual Overrides Timer times out.
(b) EXV Control Overrides can be placed into active override during normal unit operation.
Table 23. Complete list of manual override selections – cprsr control button
(a) Compressor Control Manual Override must be set to Manual before compressors are placed in manual override.
(b) Manual Override Control of Compressors are setup in Stop mode, and will only be turned On in Auto mode.
Beginning a Manual Override Event
Note: Please consider the following when applying manual overrides to the Supply and Relief
RT-SVP011E-EN
Front Panel
(a)
Lockout Cktx
Not Locked Out /
Locked Out
Front Panel
Compressor
(a)
Lockout CprsrxA
Not Locked Out /
Locked Out
EXV Control
(b)
Override
EvapxA
Auto / Manual
Condenser Reheat
Manual Override
Cktx
Auto / Manual
Compressor Control Manual
(a)
Override
Auto / Manual
(b)
Manual Enable Cprsr1A
Off / On
(b)
Manual Enable Cprsr2A
Off / On
fans. The Fan Speed Command value entered on these screens has a range of 0 to 100%.
This commanded value range equates to Minimum Speed (min%) thru Maximum Speed (Hz
or RPM) of the selected fan when the Current Value: is Manual, and the fan is operating.The
Speed Status shown is in percent where 0% equates to fan Off, (min%) equates to fan
operating at minimum speed, and 100% equates to fan operating at maximum speed. See
Table 24, p. 60
and
Figure 38, p.
Page 1
Cond Air Flow
Manual Override
Cktx
Auto / Manual
Front Panel
Compressor
(a)
Lockout CprsrxB
Not Locked Out /
Locked Out
EXV Control
(b)
Override
EvapxB
Auto / Manual
Page 2
Hot Gas Byp Valve
Manual Override
Cktx
Auto / Manual
Manual Enable Cprsr1B
Off / On
Manual Enable Cprsr2B
Off / On
60. below for example fan motor commands and status.
TD7 Display
Front Panel
Compressor
Lockout CprsrxC
Not Locked Out /
Locked Out
Manual Enable
(b)
(b)
Cprsr1C
Off / On
(b)
(a)
59