Trane IntelliPak with Symbio 800 Programming Manual page 48

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

TD7 Display
Table 17. Service settings (continued)
Value
Suction Temp. Filter Base Time
Constant
EXV Control Compressor Press Ratio
Min
EXV Control Pre-Position Hold Time
EXV Control Pre-Position Setpoint
EXV Differential Pressure Estimate Min 40.00 PSID (29.01-72.52)
EXV Feedforward Evap. Approach
Temp. Base
Ref Loss Suction Discharge Percent
Ckt1
Reference Loss Condenser Percent
Ckt1
Reference Loss Distributor Percent
Ckt1
Reference Loss Evaporator Percent
Ckt1
Reference Loss Subcooler Percent Ckt1 3.0% (0.0-10.0)
Ref Loss Suction Discharge Percent
Ckt2
Reference Loss Condenser Percent
Ckt2
Reference Loss Distributor Percent
Ckt2
Reference Loss Evaporator Percent
Ckt2
Reference Loss Subcooler Percent Ckt2 3.0% (0.0-10.0)
Condenser Reheat Softload Time
Condenser Reheat Staging Deadband 20.000 (10.000-100.000)
Cond Fan Control Reheat Diff Press
Setpoint
Cond Fan Control Cool Diff Press
Setpoint
Cond Fan Control Cool Diff Press Offset 15.00 PSID (5.00-25.00)
Cond Fan Control Cool Press Ratio
Setpoint
Condenser Fan Air Coil Correction
Cond Fan Control Efficiency Check
Point
Purge Condenser Coil Interval Setting 90 Min (60-120)
Rapid Restart Complete Temp Setting 74.0 °F (65.0-85.0)
Rapid Restart Termination Time
Rapid Restart DX Interstage Time
Rapid Restart Critical Temp Setpoint
48
Factory Default (Range)
0.0 Sec (0.0-20.0)
1.500 (1.200-1.700)
4.0 Sec (0.0-60.0)
90.0% (50.0-300.0)
9.0 °F (0.0-27.0)
2.0% (0.0-10.0)
5.0% (0.0-10.0)
15.0% (0.0-25.0)
1.0% (0.0-10.0)
2.0% (0.0-10.0)
5.0% (0.0-10.0)
15.0% (0.0-25.0)
1.0% (0.0-10.0)
120 Sec (0-1800)
250.00 PSID (85.00-300.00)
90.00 PSID (85.00-150.00)
1.55 (1.500-2.500)
11.880 (0.000-100.000)
105.0 °F (95.0-115.0)
180 Sec (120-600)
30 Sec (15-50)
90°F (75-95)
Description
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Contact Trane Technical Support.
Allows adjustment to the compressor
interstage time providing an
accelerated or delayed staging.
Used to determine the compressor
stage target during an active Rapid
Restart event.
RT-SVP011E-EN