Cooling - Trane IntelliPak with Symbio 800 Programming Manual

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

TD7 Display
Table 2.
Ventilation
Relief Fan Proving
Return Fan Run Command
Return Fan Speed Status
Return Fan Speed Command
Return Fan Proving
Relief Air Damper Command
Relief Air Damper Position
Space Static Pressure Active
Space Static Pressure Setpoint Active
Outdoor Air Flow Active
Outdoor Air Min Flow Setpoint Status
Outdoor Air Flow 1
Outdoor Air Flow 2
Discharge Air Iso Damper Command
Return Air Iso Damper Command
Return Air Iso Damper Command Pct
Space CO2 Concentration Active
Minimum Ventilation Status
Pre Evap Filter Differential Pressure
Final Filter Differential Pressure
VOM A Input
VOM B Input
VOM C Input
VOM D Input
VOM E Input
VOM Relay Status

Cooling

Touch the Cooling button to view Cooling, Circuit 1 and Circuit 2 level status information in the table
below.
The data presented in this table is unit configuration dependent.
Table 3.
Cooling
Cooling Capacity Status
Space Temp Cooling Setpoint Status
Discharge Air Temperature Active
Discharge Air Cooling Setpoint Status Compressor VFD RPM Cprsr1A
Space Temperature Active
Occupied Cooling Setpoint Active
Unoccupied Cooling Setpoint
30
Ventilation status (continued)
Cooling, Circuit 1 and Circuit 2 level status
Cooling - Circuit 1
Compressor 1A Status
Compressor 1B Status
Compressor 1C Status
Suction Pressure Ckt1
Suction Saturated Temperature Ckt1
Suction Temperature Evap1A
Cooling - Circuit 2
Compressor 2A Status
Compressor 2B Status
Compressor 2C Status
Suction Pressure Ckt2
Suction Saturated Temperature Ckt2
Suction Temperature Evap2A
Discharge Pressure Ckt2
RT-SVP011E-EN