This is the order number for the equipment that the Symbio™ 800 controller is controlling. This
number is typically entered at the factory, but can be entered in the controller.
Unit Serial Number
This number applies to the piece of equipment that the Symbio™ 800 controller is controlling. This
number is typically entered at the factory, but can be entered in the controller.
Controller Product Name
The controller product name will always be Symbio™ 800.
Controller Hardware Part Number
This is the part number for the Symbio™ 800 controller.

Operating Modes

Referring to
mode information valuable to understanding the equipment operating state. Each Unit and Circuit
mode provide sub-mode information with details to understand active controls and limits that are
affecting operation.
Figure 27. Operating Modes screen
The following unit and refrigeration circuit tables show each top level mode and list the possible
sub modes.
Table 5.
Unit
Top Level Mode
Stopped
RT-SVP011E-EN
Figure 27, p. 33
below, the Operating Modes screen provides Unit and Circuit level
Unit operation - top level mode-stopped
Description
The unit is not running. All components are turned Off and are Closed. The unit
will be allowed to run when all sources inhibiting unit operation have been
removed.
(Ex. Clearing Alarms, Timers satisfied, Releasing to Auto mode operation, etc.)