All Settings; Setpoints / Settings - Trane CCE-Compact Series Installation Operation & Maintenance

Air handling unit
Table of Contents

Advertisement

Air flow rate, duct pressure and fan speed
Power of the recovery
Valve positions and pumps for heating and cooling batteries
Humidifier
The state display shows the current operating mode / operating mode source of the AHU:
-
Start
Config
Stop / alarm
Display
BMS
Room unit
Scheduler
The different possibilities of the request (switching AHU on / off or operating mode) have different
priorities; so the AHU is switched off when the command from the display is Off, even if the sched-
uler or the BMS request is economy or comfort. The priority corresponds to the above list; "Config"
has the highest and "Scheduler" the lowest priority. Appears in the display -, then there is no re-
quest active (display, BMS and room unit have the state Auto, the scheduler is not active).

13.1 All settings

By the line All settings, the submenu All settings can be entered; by several submenus the display
pages for setpoints, operation mode, alarm state, password handling and language setting can be
entered.

Setpoints / settings

Operation mode / scheduler
Alarm states
Password handling
Language
14 Setpoints / settings
The setting of the setpoints is performed separately for the airflow rate, temperature, humidity, air
quality and night setback.
V07-19.0
no request
start phase, initialization
configuration changed; AHU blocked
AHU blocked (Alarm emergency stop)
command from operating display
command from BMS
command from room unit
command from scheduler
All settings
Setpoints/settings
Operation mode/scheduler
Alarm state
Password handling
Language
Figure 88: All settings
setpoints for temperature, humidity, air quality, ...
operation mode, scheduler, date / time setting
alarm states
enter passwords, change passwords
language selection (English, Italian, German)
1/4
English
65/115

Advertisement

Table of Contents
loading

Table of Contents