Intel® Server System M50CYP2UR Family System Integration and Service Guide
7.
Ensure that all cables are clear of the fan module keep out area on the base of the chassis.
8.
Ensure the latches on both sides of the fan module are unlocked by pulling them upward (see Letter A).
9.
Carefully lower the fan module (see Letter B). Align the two guide pins on each side of the fan module
with the latch receivers on each chassis sidewall.
10. Push down on both ends of the fan module until fully seated.
11. Push the latches on both sides of the system fan downward to lock (see Letter C).
12. Ensure each individual fan connector is fully connected by pressing down the individual fan, one at a
time (see Letter D).
13. Reinstall the air duct (see
14. Reinstall the system top cover (see
Figure 120. System Fan Assembly Installation – Part 1
Figure 121. System Fan Assembly Installation – Part 2
Section
6.2.2).
Section
6.1.2).