Siemens Synco ZW775 V2.0 Commissioning Instructions page 74

Central communication unit
Table of Contents

Advertisement

Fault input 1...20
continued
System
Fault relay 1...2
74/148
Siemens Building Technologies
HVAC Products
Command sequence: Settings > Faults > Local > Fault input 1...20
Data point
Message triggering
Default val:
Coming
Setting val:
Coming
Coming and
going
Text for: No fault
Default val:
(Blank)
Setting val:
Text
Text for: Fault
Default val:
(Blank)
Setting val:
Text
Command sequence: Settings > Faults > System
Data point
Message triggering
Default val:
Coming
Setting val:
Coming
Coming and
going
Command sequence: Settings > Faults > Fault relay > Fault relay 1...2
Data point
Fault priority
Default val:
All
Setting val:
Urgent
Not urgent
All
Fault source
Fault relay 1
Default val:
Fault local (acoustic)
Fault relay 2
Default val:
Fault system (acoustic)
Setting val relay 1 and 2:
Fault local (visual)
Fault local (acoustic)
Fault system (acoustic)
Commissioning instructions OZW775 V2.01
Parameterize OZW775
Explanation, example
"Coming" => a message is triggered when a
fault is received (start of fault).
"Coming and going" => a corresponding
message is triggered at the start and end of a
fault.
LED "Local" indicates a fault at a fault input.
Text input comprising max. 20 alphanumeric
characters. If there is no other entry, message
text "[Fault inp 1...20] n flt" applies.
Text input comprising max. 20 alphanumeric
characters. If there is no other entry, message
text "[Fault inp 1...20] fault" applies.
Explanation, example
"Coming" => a message is triggered when a
fault is received (start of fault).
"Coming and going" => a corresponding
message is triggered at the start and end of a
fault.
This "Message triggering" applies to device
faults on the KNX network (system) sent via bus
to the central communication unit. The LED
"System" indicates a fault "System".
Explanation, example
Setting value "All" means that the fault relays
are controlled for all types of faults (Urgent and
Not urgent).
Setting values "Urgent" and "Not urgent" are
used as a filter, i.e. the fault relays are only
controlled if there is a fault with relevant "Fault
priority".
Use setting values "Local" and "System" as
separators to control the fault relays.
Setting value "Local" controls "Fault relay 1" or
"Fault relay 2" only for "Local" faults.
Accordingly, "Fault relay 1" or "Fault relay 2" are
controlled only for "System" faults.
CE1C5663en
22.06.2012