Siemens Synco ZW775 V2.0 Commissioning Instructions page 67

Central communication unit
Table of Contents

Advertisement

Message receiver 1...4
continued
Siemens Building Technologies
HVAC Products
Command sequence: Settings > Message receiver > Message receiver 1...4
Data points "Phone number provider" and "Hardware settings" are displayed if:
• Receiver type
• Interface
• Modem type
• Transmission protocol
Data point
Phone number provider
Default val:
(Blank)
Setting val:
Max. 20 characters
Hardware settings
Default val:
7E1
Setting val:
7E1, 8N1
Data point "Display format" is displayed if:
• Receiver type
• Interface
• Modem type
• Transmission protocol
Data point
Display format
Default val:
Alphanumeric
(160 characters)
Setting val:
Alphanumeric
(40 characters)
Alphanumeric
(80 characters)
Alphanumeric
(160 characters)
Data points "Service number" and "Receiver key word" (see next page) are displayed if:
• Receiver type
• Interface
• Modem type
• Transmission protocol
Data point
Service number
Default val:
(Blank)
Setting val:
Max. 20 characters
Commissioning instructions OZW775 V2.01
Parameterize OZW775
= Mobile phone / pager
= Modem
= Analog / ISDN
= TAP / UCP
Explanation, example
The setting value corresponds to the phone
number assigned by the external telephone
provider (e.g. Swisscom) to send messages.
The data point is not displayed if "Modem type =
GSM", as the central communication unit can
then read the phone number from the SIM card.
The setting value depends on the phone service
provider. Meaning:
st
1
digit:
Number of data bits
Letter:
Parity (Even, None)
nd
2
digit:
Number of stop bits.
= Pager
= Modem
= Analog / ISDN / GSM
= TAP / SMS GSM service
Explanation, example
The setting value corresponds to the number of
alphanumeric characters, matched to the pager.
Note: The central communication unit does not
support pagers with only 20 characters.
= Fax / pager
= Modem
= GSM
= SMS GSM service
Explanation, example
The setting value corresponds to the service
number specified by the external phone service
provider for certain services. The service
number is also referred to as target number.