7.4 Error code list for the central communication
unit
Error
Faults of the central communication unit
code no.
and associated fault text in ACS
0
No fault
1
Plant ok
2
Fault
3
No urgent fault
101...108 [N.X1] ... [N.X8] sensor error
5000
No bus power supply
5001
System time failure (OZW775 as slave)
5002
> 1 clock time master
5003
Invalid time of day (time OZW775 not set/set incorrectly)
5012
Device failure (bus)
5021
No modem communication
5023
Message receiver 1 not reached
5024
Message receiver 2 not reached
5025
Message receiver 3 not reached
5026
Message receiver 4 not reached
6001
>1 identical device address
(devices with identical address)
9001
[Fault input 1] Fault
...
...
9020
[Fault input 20] Fault
1911
[Optg hours 1] service required
...
...
(Operating hours for service reached)
1915
[Optg hours 5] service required
7251
Bus module not identified
1)
Device failure (bus) is a "System fault" sent by the central communication unit. This is why it is listed
in this table. The central communication unit only detects all other "System faults" and indicates them
depending on parameterization.
Commissioning instructions OZW775 V2.01
Appendix
Faults
Sensors
Communication
1)
System error configuration
Miscellaneous errors
Type of fault
No acknowledgement
No acknowledgement
No acknowledgement
No acknowledgement
No acknowledgement
No acknowledgement
No acknowledgement
Acknowledgment
No acknowledgement
No acknowledgement
No acknowledgement
No acknowledgement
No acknowledgement
No acknowledgement
No acknowledgement
Acknowledgment
No acknowledgement
or acknowledgement
after setting
No acknowledgement
No acknowledgement