Siemens Synco ZW775 V2.0 Commissioning Instructions page 56

Central communication unit
Table of Contents

Advertisement

Time switch
continued
Meter
Operating hours
56/148
Siemens Building Technologies
HVAC Products
Command sequence: Commissioning > Extra configuration > Time switch
Data point
[Time switch 1...4]
op selector
Default val:
Yes
Setting val:
No, Yes
Command sequence: Commissioning > Extra configuration > Meter
Data point
Input 1...8
Default val:
---
Setting val:
---, N.X1...N.X8
Displayed unit
Default val:
kWh
Setting val:
Wh, kWh, MWh,
kJ, MJ, GJ, ml, l, m3, Heat cost
unit, No unit, BTU
Displayed format
Default val:
0
Setting val:
0, 0.0, 0.00, 0.000
Command sequence: Commissioning > Extra configuration > Operating hours
Data point
Input 1...5
Default val:
---
Setting val:
---, N.X1...N.X8
N.D1...N.D8
Commissioning instructions OZW775 V2.01
Parameterize OZW775
Explanation, example
Each [time switch 1...4] is preconfigured with
"Op selector = Yes". Setting value "No"
deactivates the operating selector.
Explanation, example
You must configure value "Pulse" at the "Input
identifier" for data points N.X1...N.X8 before you
can set value N.X1...N.X8 at input 1...8.
Setting value N.X_ connects input 1...8 of FB
"Meter" to the terminal input to which the
counter pulse contact is connected (or
configured at data point N.X_ with "Pulse").
Setting value Wh, kWh, ... helps (for input 1...8
of FB "Meter") align the "Displayed unit" in ACS
and that of the meter (device).
Setting value 0, 0.0, ... helps (for input 1...8 of
FB "Meter") align the "Displayed format" in ACS
and that of the meter (device).
Explanation, example
Setting value N.X_ or N.D_ connects input 1...5
of FB "Operating hours" to the terminal input to
which the operation status contact is connected.
-{}
-
CE1C5663en
22.06.2012