Siemens Synco ZW775 V2.0 Commissioning Instructions page 54

Central communication unit
Table of Contents

Advertisement

Interfaces
PC
Modem
Ethernet
KNX
54/148
Siemens Building Technologies
HVAC Products
The central communication unit has three interfaces to communicate between unit and
user, and an interface or connection for the KNX bus.
The "PC" interface is intended to directly connect a central communication unit to a
local operator station. A USB cable, type A-B, is required to this end.
The "Modem" interface helps connect a modem via RS-232. When communicating via
modem, the following message receivers are supported: Operator stations (PC/laptop
with ACS software), SMS receivers, pagers, fax machines.
The interface labeled "Ethernet" corresponds to a RJ45 plug on the Ethernet card
OZZ7E5. Order the card separately and insert it in the central communication unit. You
need a network cable Cat-5 to connect to the Ethernet (Ethernet category 5 cable).
The CE+ and CE- connection terminals labeled "KNX" are for the KNX bus. See data
sheet N3127 for more information on the KNX bus.
Commissioning instructions OZW775 V2.01
Parameterize OZW775
CE1C5663en
22.06.2012