Step
Section
5
3.1
6
3.2
3.2.1
3.2.2
14/148
Siemens Building Technologies
HVAC Products
Description
Create new plant
Workflow:
1.
Plant > New > Plant....
.
2.
Enter plant name.
3.
Describe plant (optional).
4.
Select unit type "OZW775" in "Communication" dialog box.
5.
Keep code number 01 and interface "USB".
6.
Refresh device list, click
7.
Open the
via
[Popcard]
8.
Expand menu tree and check devices in the folder list.
Does the folder list contain all desired device = Yes / No:
Yes
 Continue at step 7
No
 Continue at step 6
Note:
After you create a new plant, the central communication unit is in "Commissioning
mode = On" (not normal operation). Carry out the next steps under "Commissioning
mode = On".
Edit device list
Create device list
"Create device list" is always required after creating a new plant.
Workflow:
1.
Select
Plant > Edit device list...
Device address 150
2.
Right-click
menu and then select
3.
Check the devices in the "List of assigned devices".
Does the folder list contain all desired device = Yes / No:
Yes
 Continue at step 7
No
 Devices from other lines/areas are missing; see "Add devices"
No
 List contains unwanted devices; see "Delete devices"
Note:
Command
Create device list
list contains the central communication unit and the devices integrated in the line (or
area) of the central communication unit.
Add devices
Needed to add devices from other lines and/or areas.
Prerequisite:
Plant > Edit device list...
Workflow:
1.
Right-click the "List of assigned devices" field to open the context menu and then
select
Add devices...
.
2.
The "Add device" dialog box opens. Click
3.
The "Add/change device" dialog box opens. Enter the address values.
4.
Click
to confirm the entered address values.
Add
5.
Add the device(s) to the device list by clicking
devices" dialog box.
6.
Close the
ACS operation – [Edit device list]
7.
Select
Applications > Popcard...
contains the device(s).
Commissioning instructions OZW775 V2.01
Recommended commissioning
.
Yes
.
Applications > Popcard...
.
(= central communication unit) to open the context
Create device list
.
creates and displays the "List of assigned devices". The
already selected.
Add device
dialog box.
to open the
[Popcard]
.
in the "Insert
Write device list
and check if the device list
CE1C5663en