Siemens Synco ZW775 V2.0 Commissioning Instructions page 20

Central communication unit
Table of Contents

Advertisement

Step
Section
13
4.7
(continued)
4.7.3
4.7.4
14
5.1
5.1.1
15
5.2
5.2.1
5.2.2
5.2.3
16
5.3
5.3.1
5.3.2
5.3.3
5.3.4
20/148
Siemens Building Technologies
HVAC Products
Description
Application [ Popcard ] "Commissioning mode = Off"  Normal operation
Data points in the "Device information" operating page
Command sequence:
Device information
> Central communication unit
> Konnex
Data point "Time of day/date"
Data point "Time of day/date" is displayed multiple times and can be set in the
following applications:
[ Popcard ] "Commissioning mode = Off" Operating page "Commissioning"
[ Popcard ] "Commissioning mode = Off" Operating page "Time / Date"
[ Popcard ] "Commissioning mode = On" Operating page "Commissioning"
 Set current data and time; see Section 5.4.1.
Tests following parameterization
Commissioning mode "On / Off"
"Commissioning mode = On" must be set to prevent events from being triggered
during testing (no state changes in the plants).
After you complete the wiring and communication tests, you must reset to
"Commissioning mode = Off" prior to starting normal mode.
Wiring test
Wiring test active "Yes / No"
"Wiring test active = Yes" must be set to be able to test the wiring at the inputs and
outputs.
Set again "Wiring test active = No" after you finish the wiring tests.
Wiring test for inputs
You can test inputs N.X1...N.X8 and N.D1...N.D8.
Wiring test for outputs
You can test outputs "Time switch 1...4" and "Fault relay 1...2".
Test message receiver
Communication to the message receiver
Test communication (possible with "Commissioning mode = On / Off");
see Section 5.3.1 for workflow.
Diagnose communication via modem
Test modem connection (possible with "Commissioning mode = On / Off");
see Section 5.3.2 for workflow.
Modem message interval
The time the central communication unit must wait between communication abortion
and reestablishing communication when connected via modem.
Error codes for modem communication
Commissioning instructions OZW775 V2.01
Recommended commissioning
Data points
...
Central comm unit type
Software version (firmware)
Hardware version
...
Number of devices max
Number of devices min
Last change
CE1C5663en
22.06.2012