6.3.3 E-mail message receiver

Configure the following data points to send e-mails in FB "Message receiver" for
receivers 1...4 (1...4, depending on the number of PC/laptops with e-mail reception).
Command sequence: Settings > Message receiver > Message receiver 1...4
Data point
Message receiver 1...4
Default val:
(Blank)
Setting val:
Name
Receiver type
Default val:
---
Setting val:
E-mail.
Interface
Default val:
USB
Setting val:
Ethernet
Transmission protocol
Default val:
ACS protocol
Setting val:
SMTP
Fault priority
Default val:
All
Setting val:
All, Only urgent
faults
E-mail address
Default val:
name@example.com
Setting val: E-mail address
Check communication after you configure the data points. See Section 5.3.
Send a test system report to a message receiver. If the test is successful, data point
"System report sent" confirms with "Yes".

6.3.4 Diagnosis: Send e-mails

Use the following steps to diagnose problems if sending e-mails causes errors or if e-
mails are not sent.
Is the network containing the web server connected to DNS server 1 (and DNS
server 2)?
• Check using the PC/laptop on the same network (the network containing the web
server OZwW775) by entering the following ping or nslookup command:
ping <IP address DNS server>
nslookup <IP address DNS server> or nslookup <Domain DNS server>
See next page for Steps 2 to 6.
Commissioning instructions OZW775 V2.01
Communication via Ethernet
Project information
Name (text, max. 20 alphanumeric characters).
..........................................................................
Only the following setting is valid to send e-mails:
Receiver type = E-mail.
Only the following setting is valid to send e-mails:
Interface= Ethernet.
Only the following setting is valid to send e-mails:
Transmission protocol = SMTP.
Valid "All" or "Only urgent". Setting if not default:
..........................................................................
E-mail address of the receiver (max. 20 characters).
..........................................................................
or ping <Domain DNS server>